Technical Specification |
SUN2000 -10KTL-M0 |
Efficiency |
Max. efficiency |
0.986 |
European weighted efficiency |
0.981 |
Input |
Recommended max. PV power |
14,880 Wp |
Max. input voltage 1 |
1,100 V |
Operating voltage range 2 |
140 V ~ 980 V |
Start-up voltage |
200 V |
Full power MPPT voltage range |
470 V ~ 850 V |
Rated input voltage |
600 V |
Max. input current per MPPT |
11 A |
Max. short-circuit current |
15 A |
Number of MPP trackers |
2 |
Max. input number per MPP tracker |
1 |
Output |
Grid connection |
Three-phase |
Rated output power |
10,000 W |
Max. apparent power |
11,000 VA 3 |
Rated output voltage |
220 Vac / 380 Vac, 230 Vac / 400 Vac, 3W / N+PE |
Rated AC grid frequency |
50 Hz / 60 Hz |
Max. output current |
16.9 A |
Adjustable power factor |
0.8 leading ... 0.8 lagging |
Max. total harmonic distortion |
≤ 3 % |
Features & Protections |
Input-side disconnection device |
Yes |
Anti-Islanding protection |
Yes |
DC reverse polarity protection |
Yes |
Insulation monitoring |
Yes |
DC surge protection |
Yes, compatible TYPE II protection class according to EN/IEC 61643-11 |
AC surge protection |
Yes, compatible TYPE II protection class according to EN/IEC 61643-11 |
Residual current monitoring |
Yes |
AC overcurrent protection |
Yes |
AC short-circuit protection |
Yes |
AC overvoltage protection |
Yes |
Arc fault protection |
Yes |
Ripple receiver control |
Yes |
DC MBUS to optimizer |
No |
General Data |
Operating temperature range |
-25 ~ + 60 °C (-13 °F ~ 140 °F) |
Relative operating humidity |
0 %RH~100 %RH |
Operating altitude |
0 - 4,000 m (13,123 ft.) (Derating above 3000 m) |
Cooling |
Natural convection |
Display |
LED Indicators; Integrated WLAN + FusionSolar App |
Communication |
RS485; |
|
RS485; WLAN/Ethernet via Smart Dongle-WLAN-FE; 4G / 3G / 2G via Smart Dongle-4G (Optional) |
Weight (incl. mounting bracket) |
17 kg (37.5 lb) |
Dimension (incl. mounting bracket) |
525 x 470 x 166 mm (20.7 x 18.5 x 6.5 inch) |
Degree of protection |
IP65 |
Nighttime Power Consumption |
< 5.5 W |
Standard Compliance (more available upon request) |
Certificate |
EN/IEC 62109-1, EN/IEC 62109-2 |
Grid connection standards |
G98, G99, EN 50438, EN50549-1, CEI 0-21, VDE-AR-N-4105, AS 4777, C10/11, ABNT, UTE C15-712, RD 1699, TOR D4, |
|
IEC61727, IEC62116, DEWA |