| Technical Specification |
SUN2000 -10KTL-M0 |
| Efficiency |
| Max. efficiency |
0.986 |
| European weighted efficiency |
0.981 |
| Input |
| Recommended max. PV power |
14,880 Wp |
| Max. input voltage 1 |
1,100 V |
| Operating voltage range 2 |
140 V ~ 980 V |
| Start-up voltage |
200 V |
| Full power MPPT voltage range |
470 V ~ 850 V |
| Rated input voltage |
600 V |
| Max. input current per MPPT |
11 A |
| Max. short-circuit current |
15 A |
| Number of MPP trackers |
2 |
| Max. input number per MPP tracker |
1 |
| Output |
| Grid connection |
Three-phase |
| Rated output power |
10,000 W |
| Max. apparent power |
11,000 VA 3 |
| Rated output voltage |
220 Vac / 380 Vac, 230 Vac / 400 Vac, 3W / N+PE |
| Rated AC grid frequency |
50 Hz / 60 Hz |
| Max. output current |
16.9 A |
| Adjustable power factor |
0.8 leading ... 0.8 lagging |
| Max. total harmonic distortion |
≤ 3 % |
| Features & Protections |
| Input-side disconnection device |
Yes |
| Anti-Islanding protection |
Yes |
| DC reverse polarity protection |
Yes |
| Insulation monitoring |
Yes |
| DC surge protection |
Yes, compatible TYPE II protection class according to EN/IEC 61643-11 |
| AC surge protection |
Yes, compatible TYPE II protection class according to EN/IEC 61643-11 |
| Residual current monitoring |
Yes |
| AC overcurrent protection |
Yes |
| AC short-circuit protection |
Yes |
| AC overvoltage protection |
Yes |
| Arc fault protection |
Yes |
| Ripple receiver control |
Yes |
| DC MBUS to optimizer |
No |
| General Data |
| Operating temperature range |
-25 ~ + 60 °C (-13 °F ~ 140 °F) |
| Relative operating humidity |
0 %RH~100 %RH |
| Operating altitude |
0 - 4,000 m (13,123 ft.) (Derating above 3000 m) |
| Cooling |
Natural convection |
| Display |
LED Indicators; Integrated WLAN + FusionSolar App |
| Communication |
RS485; |
| |
RS485; WLAN/Ethernet via Smart Dongle-WLAN-FE; 4G / 3G / 2G via Smart Dongle-4G (Optional) |
| Weight (incl. mounting bracket) |
17 kg (37.5 lb) |
| Dimension (incl. mounting bracket) |
525 x 470 x 166 mm (20.7 x 18.5 x 6.5 inch) |
| Degree of protection |
IP65 |
| Nighttime Power Consumption |
< 5.5 W |
| Standard Compliance (more available upon request) |
| Certificate |
EN/IEC 62109-1, EN/IEC 62109-2 |
| Grid connection standards |
G98, G99, EN 50438, EN50549-1, CEI 0-21, VDE-AR-N-4105, AS 4777, C10/11, ABNT, UTE C15-712, RD 1699, TOR D4, |
| |
IEC61727, IEC62116, DEWA |
1 The maximum input voltage is the upper limit of the DC voltage. Any higher input DC voltage would probably damage inverter.
*2 Any DC input voltage beyond the operating voltage range may result in inverter improper operating. |